BS EN 50228-7 Cable · 01
No.LayerKey Materials/ RequirementsFunction
1ConductorConductors shall be plain annealed copper wires which are solid (Class 1), stranded (Class 2) or flexible (Class 5).Tinned copper is optional.Current-carrying core for power transmission
2Insulation1.PVC (polyvinyl chloride) 2.PE (polyethylene) 3.XLPE (cross‑linked polyethylene) 4.EPR (ethylene propylene rubber)Electrical isolation to prevent leakage current
3ScreeningTwo insulated conductors are uniformly twisted to form pairs which are then assembled. The paired conductors may be : a.Unscreened b.individually and overall screened c.Overall screened Screening materials can be aluminium tape, copper tape,or copper wire braiding as per customers’ specification.Suppress external electromagnetic interference from entering the cable (resistance to external interference).
4ArmouringInstrumentation cables may be armoured or non armoured. Armouring which basically serves as mechanical protection can be in the form galvanized steel wire, tape or braiding wire.Provides mechanical protection as its primary function, with additional secondary functions.
5SheathingPVC (polyvinyl chloride) LSOH (Low Smoke Halogen Free) PE (polyethylene) EVA (ethylene vinyl acrylate) EMA (ethylene methyl acrylate)Provides environmental protection for cable internal components, featuring abrasion‑resistance, moisture‑proof and ageing‑resistance. It shall not serve as primary electrical insulation.